Ethernet & 4-20 mA Output RTD Temperature Transmitter

Exceptional linearity & accuracy at high update rates. DIN Rail mounted, digitally programmable.
Ethernet transmitter

Features

  • Ethernet data I/O, Modbus TCP protocol.
  • 4-20 mA or 0-10V transmitter output, 16 bits, jumper selectable, isolated.
  • Dual 120 mA solid state relays for alarm or control, isolated.
  • Factory calibrated for 100Ω platinum, 10Ω copper and 120Ω nickel RTDs.
  • 2, 3 or 4-wire RTD connection for lead resistance compensation.
  • User selectable input span from entire RTD range down to 15.0°.
  • Analog output resolution 0.0015% of span (16 bits), accuracy ±0.02% of span.
  • Fast update rate to 50 or 60 per second.
  • Universal 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac power.
  • DIN rail mount housing only 22.5 mm wide, detachable screw-clamp connectors.
  • -X extended operating temperature option from -40°C to 70°C
Description

The Laureate RTD temperature transmitter and signal conditioner provides a linearized, highly accurate, stable and repeatable transmitter output for 100 ohm platinum, 10 ohm copper and 120 ohm nickel RTDs. Pt100 platinum RTDs can have a DIN alpha of 0.00385 or ANSI alpha of 0.00392. The RTD type and temperature range, specified in °C or °F, are user-selectable. The temperature range can be as wide as the entire span of the RTD type or as narrow as 150 counts (such as 15.0°), limited only by considerations of electrical noise and digital filtering time constants.

RTD signal conditioner board

Digital calibration of all RTD ranges is performed the factory, with calibration data stored in EEPROM on the signal conditioner board. This allows signal conditioner boards and ranges to be changed in the field with no need for recalibration. Typical accuracy for a Pt100 is better than ±0.04°C (±0.07°F) ±0.01% of reading. RTD excitation is provided by the transmitter. RTD connections can be of the 2-, 3- or 4-wire type. With 3- and 4-wire connections, the transmitter automatically compensates for changes in lead resistance to the sensor.

Fast read rate at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle is provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion. High read rate is ideal for peak or valley capture and for real-time computer interface and control.

Standard features of Laureate LTE transmitters include:

  • Ethernet I/O, isolated. The supported protocols are Modbus RTU and ASCII, which are tunneled via Modbus TCP. Note that RS232 or RS485 data I/O is provided by Laurel's LT Series transmitters.
  • 4-20 mA, 0-20 mA or 0-10V analog transmitter output, isolated, jumper-selectable and user scalable. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500 ohm (or lower) load for 10V compliance, or 10V into a 5K ohm (or higher) load for 2 mA compliance.
  • Dual solid state relays, isolated. Available for local alarm or control. Rated 120 mA at 130 Vac or 180 Vdc.
  • Universal 85-264 Vac power. Low-voltage 10-48 Vdc or 12-32 Vac power is optional.

Node discovery and configuration of Laureate Ethernet transmitters are easily achieved with Laurel's Windows based Instrument Setup Software. Additional features are provided by Laurel's Windows based Node Manager Software, such as the ability to send emails or test messages either periodically or in the event of an alarm. Both softwares run on a PC under MS Windows, are at no charge, and can be downloaded from this website.

Laureate Ethernet network by Laurel Electronics
Specifications
RTD Metal Alpha R at 0°C R at top
of range
Excitation
Current
Range Max Error
Platinum
Pt100
0.003850 (DIN) 100Ω 390.48Ω
at 850°C
196 µA -202°C to +850°C
-331°F to +1562°F
±0.03°C ±0.01% of rdg
±0.05°F ±0.01% of rdg
Platinum
Pt100
0.003902 (ANSI) 100Ω 394.36Ω
at 850°C
196 µA -202°C to +850°C
-331°F to +1168°F
±0.04°C ±0.01% of rdg
±0.07°F ±0.01% of rdg
Nickel
Ni120
0.00672 120Ω 380.31Ω
at 260°C
196 µA -80°C to +260°C
-112°F to +500°F
±0.05°C ±0.01% of rdg
±0.09°F ±0.01% of rdg
Copper
Cu10
0.00427 9.035Ω 19.116Ω
at 260°C
5.0 mA -100°C to +260°C
-148°F to +500°F
±0.05°C ±0.01% of rdg
±0.09°F ±0.01% of rdg
RTD Input
Calibration, Pt 100 DIN IEC 751 (IPTS-68)
Calibration, Pt 100 ANSI NIST Monograph 126
Configuration 2, 3 or 4-wire connection
Excitation current 0.2 mA
Max error at 25°C, Pt100 ±0.04°C (±0.07°F) ±0.01% of reading
Span tempco ±0.003% of reading/°C
Zero tempco ±0.03 deg/deg
Sensor lead resistance 2-wire: 10 mdeg/Ω/deg up to 10Ω;
tempco per conductor 3 & 4-wire: 10 μdeg/Ω/deg up to 100Ω
Over-voltage protection 125 Vac
Open sensor indication 0 mA or > 20 mA output, selectable
Provision for user calibration Multiplier of RTD resistance plus offset in degrees
Analog Output (standard)
Output Levels 4-20 mA and 0-10 Vdc (selectable)
Compliance, 4-20 mA 10V (0-500Ω load)
Compliance, 0-10V 2 mA (5 kΩ load)
Output Resolution 16 bits (65,536 steps)
Output Accuracy ±0.02% of output span
Output Isolation 250V rms working, 2.3 kV rms per 1 minute test
Step response time 50 ms
Ethernet Data I/O (standard)
Type 10/100Base-T Ethernet per IEEE 802.3
Data Rates 300, 600, 1200, 2400, 4800, 9600, 19200 baud
Output Isolation 250V rms working, 2.3 kV rms per 1 min test
Serial Protocol Modbus TCP
Modbus Compliance Modbus over Serial Line Specification V1.0 (2002)
Digital Addresses 247 for Modbus
Dual Relay Output (standard)
Relay Type Two solid state relays, SPST, normally open, Form A
Load Rating 120 mA at 140 Vac or 180 Vdc
Power Input
Standard Power 85-264 Vac or 90-300 Vdc
Low Power Option 10-48 Vdc or 12-32 Vac
Power Frequency DC or 47-63 Hz
Power Isolation 250V rms working, 2.3 kV rms per 1 min test
Power Consumption 2.5W typical at 24V
Mechanical
Dimensions 129 x 104 x 22.5 mm case
Mounting 35 mm rail per DIN EN 50022
Electrical Connections Plug-in screw-clamp connectors
Environmental
Operating Temperature 0°C to 55°C standard, -40°C to 70°C with -X option
Storage Temperature -40°C to 85°C
Relative Humidity 95% at 40°C, non-condensing
Cooling Required Mount transmitters with ventilation holes at top and bottom. Leave 6 mm (1/4") between transmitters, or force air with a fan.
Pinout
Laureate™ Ethernet & 4-20 mA Output RTD Temperature Transmitter and Signal Conditioner
LTE Ethernet transmitter pinout, analog input

RTD hookup can be via 2, 3 or 4 wires to the J5 connector. The transmitter applies an excitation current of 196 µA (Pt 100 and Ni 120) or 5 mA (Cu 10).

4-wire hookup of RTD signal conditioner board In 4-wire hookup, different pairs of leads are used to apply the excitation current and sense the voltage drop across the RTD, so that the IR drop across the excitation leads is not a factor.
3-wire hookup of RTD signal conditioner board In 3-wire hookup, the transmitter senses the combined voltage drop across the RTD plus two excitation leads. It also senses the voltage drop across one excitation lead, and then subtracts twice this voltage from the combined total. This technique effectively subtracts all lead resistance and compensates for ambient temperature changes if the two excitation leads are identical.
2-wire hookup of RTD signal conditioner board In 2-wire hookup, the transmitter senses the combined voltage drop across the RTD and both lead wires. The voltage drop across the lead wires can be measured by shorting out the RTD during transmitter setup, and this voltage is then automatically subtracted from the combined total. However, changing resistance of the lead wires due to ambient temperature changes will not be compensated.
Applications

Operation as a Fast ON/OFF Controller or Supervisory Monitor

Temperature controller operation of Laureate temperature meters and transmitters With the optional dual solid state relay output option, which has a typical response time of only 17 ms, Laureate temperature meters and transmitters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control. They can also serve as supervisory process monitors and provide alarms or shutoffs when processes exceed normal limits.
For applications assistance, phone 714-434-6131 ext. 104, or email support@laurels.com
Ordering Guide
Laureate™ Ethernet & 4-20 mA Output RTD Temperature Transmitter and Signal Conditioner
Click on the radio buttons to build a model number with pricing as shown below. Prices are in US dollars and do not include shipping or duty charges (export sales). Please see our explanations and limitations applicable to pricing and online orders. Prices shown are in US Dollars and are Laurel's manufacturer's suggested retail price (MSRP) in the USA. Orders are processed manually, not directly by our shopping cart system. You don't have to supply credit card information when placing an online order.

North American Orders. Laurel does not sell factory-direct in the USA or Canada. Online sales orders are filled through distribution. During the ordering process, you will have the chance to select an authorized Laurel distributor, or you can ask Laurel to refer you to a distributor. The distributor will then contact you to quote shipping, tax and duty (where applicable), and arrange for payment.

International Orders. If your ship-to address indicates that you are outside of the USA or Canada and Laurel has a distributor in your country, we will forward your order to that distributor for follow-up. If Laurel does not have a distributor in your country, we will email you an order acknowledgment and a pro forma invoice which states the product price, shipping charges, and wire transfer information, which includes a $25 bank wire transfer fee.

Questions about your order? Please email your distributor or ventas@laurelsmexico.com
 
Quantity
Transmitter Type LTE  4-20 mA & Ethernet outputs transmitter $388
LT  4-20 mA & RS232/RS485 outputs transmitter $164
Main Board 2  Standard analog input. $0
Power 0  Isolated 85-264 Vac or 90-300 Vdc $89
1  Isolated 12-32 Vac or 10-48 Vdc $89
RTD Input P385C  Pt 100 DIN RTD, -202°C to 850°C $81
P385F  Pt 100 DIN RTD, -331°F to 1562°F $81
P392C  Pt 100 ANSI RTD, -202°C to 631°C $81
P392F  Pt 100 ANSI RTD, -331°F to 1168°F $81
N672C  Ni 120 RTD, -100°C to +260°C $81
N672F  Ni 120 RTD, -148°F to +500°F $81
C427C  Cu 10 RTD, -100°C to +260°C $81
C427F  Cu 10 RTD, -148°F to +500°F $81
Note: The same signal conditioner board can be user configured for all RTD types listed and °C or °F, as well as for resistance measurement.  
Add-on Options -X  Extended operating temperature option from -40°C to 70°C $33
 
Configured model number LTE20P385C
Configured price per model $558
Quantity 1
Extended price $508