The Laureate dual-channel up or down totalizer is a basic operating mode of the Laureate counter with the FR dual-channel signal conditioner board. Each channel (A or B) may be independently set up and scaled to count up from zero (or other value) to a preset limit, or to count down from a preset value to zero (or other limit). Countdown operation is set up by entering a negative scale factor.
The six-digit counter display is capable of displaying any value from -999,999 to 999,999 with a programmable decimal point. Scaling allows direct readout in engineering units, such as gallons or cubic feet based on counts from a turbine flowmeter, or the count of cans based on the count of six-packs. The displayed channel (A or B) is selected via a front panel pushbutton. The totals are stored in non-volatile memory so as to be retained in the absence of power.
The minimum recommended complementary option for the Laureate totalizer is the dual setpoint controller output board, which is available with either 8A relays or AC/DC solid state relays.
An optional Extended counter version provides capabilities beyond those of the Standard counter:
The FR dual-channel signal conditioner accepts inputs from proximity switches with a PNP or NPN output, TTL or CMOS logic, magnetic pickups, contact closures, low-level outputs from turbine flow meters down to 12 mV, and high-level AC line inputs up to 250 Vac. Jumper selections provide optimum operation for different sensor types and noise conditions. A built-in isolated 5, 10, or 24 Vdc excitation supply can power proximity switches and other sensors, and eliminate the need for an external power supply.
Designed for system use. Optional plug-in boards for communications and control include Ethernet, WiFi and serial communication boards, dual or quad relay boards, and an isolated analog output board. Laureates may be powered from 85-264 Vac or optionally from 12-32 Vac or 10-48 Vdc. The display is available with red or green LEDs. The 1/8 DIN case meets NEMA 4X (IP65) specifications from the front when panel mounted. Any setup functions and front panel keys can be locked out for simplified usage and security. A built-in isolated 5, 10, or 24 Vdc excitation supply can power transducers and eliminate the need for an external power supply. All power and signal connections are via UL / VDE / CSA rated screw clamp plugs.
Display | |
---|---|
Readout | 6 LED digits, 7-segment, 14.2 mm (.56"), red or green. |
Color | Red or green LED |
Display Range | -999999 to +999999, XXXXEX notation beyond 999999 |
Zero Adjust | -999999 to +999999 |
Span Adjust | 0 to 999999 |
Indicators | Four LED lamps |
Inputs | |
Types | AC, pulses from NPN, PNP transistors, contact closures, magnetic pickups. |
Signal Ground | Common ground for channels A & B |
Channel A Freq. | 0 Hz to 1 MHz |
Channel B Freq. | 0 Hz to 250 kHz |
Minimum Signal | Nine ranges from (-12 to +12 mV) to (+1.25 to +2.1V). |
Maximum Signal | 250 Vac |
Noise Filter | 1 MHz, 30 kHz, 250 Hz (selectable) |
Contact Debounce | 0, 3, 50 ms (selectable) |
Excitation Output (standard) | |
5 Vdc | 5 Vdc ± 5%, 100 mA |
10 Vdc | 10 Vdc ± 5%, 120 mA |
24 Vdc | 24 Vdc ± 5%, 50 mA |
Output Isolation | 50 Vdc to meter ground |
Power Supply Boards (one required) | |
Voltage, standard | 85-264 Vac or 90-300 Vdc |
Voltage, optional | 12-32 Vac or 10-48 Vdc |
Frequency | DC or 47-63 Hz |
Power consumption (typical, base meter) | 1.2W @ 120 Vac, 1.5W @ 240 Vac, 1.3W @ 10 Vdc, 1.4W @ 20 Vdc, 1.55W @ 30 Vdc, 1.8W @ 40 Vdc, 2.15W @ 48 Vdc |
Power Isolation | 250V rms working, 2.3 kV rms per 1 min test |
Analog Output Boards (one optional) | |
Output levels | 4-20 mA, 0-20 mA, 0-10V, -10 to +10V (single-output option) |
4-20 mA, 0-20 mA, 0-10V (dual-output option) | |
Current compliance | 2 mA at 10V ( > 5 kΩ load) |
Voltage compliance | 12V at 20 mA (< 600 Ω load) |
Scaling | Zero and full scale adjustable from -99999 to +99999 |
Resolution | 16 bits (0.0015% of full scale) |
Isolation | 250V rms working, 2.3 kV rms per 1 min test |
(dual analog outputs share the same ground) | |
Relay Output Boards (one optional) | |
Dual magnetic relays | 2 Form C, 8A at 250 Vac or 24 Vdc, 0.3A at 250 Vdc, resistive load |
Quad magnetic relays | 4 Form A (NO), 8A at 250 Vac or 24 Vdc, 0.3A at 250 Vdc, resistive load |
Dual solid state relays | 2 Form A (NO), 120 mA at 140 Vac or 180 Vdc, resistive load |
Quad solid state relays | 4 Form A (NO), 120 mA at 140 Vac or 180 Vdc, resistive load |
Relay commons | Isolated commons for dual relays or each pair of quad relays |
Relay isolation | 250V rms working, 2.3 kV rms per 1 minute test |
Relay latching modes | Latching or non-latching |
Relay active modes | Active on or off, active high or low |
Hysteresis modes | QA passband mode, split hysteresis, span hysteresis |
Communication Boards (one optional) | |
Board selections | RS232, RS485 with dual RJ11 connectors, RS485 with dual RJ45 connectors, USB, Ethernet, USB-to-RS485 gateway, Ethernet-to-RS485 gateway, WiFi with built-in antenna plus USB & RS485, WiFi with external antenna plus USB & RS485 |
Protocols | Laurel Custom ASCII (serial), Modbus RTU (serial), Modbus TCP (Ethernet or WiFi) |
Digital addresses | 247 (Modbus), 31 (Laurel ASCII), |
Isolation | 250V rms working, 2.3 kV rms per 1 min test |
Environmental | |
Operating temperature | 0°C to 55°C |
Storage temperature. | -40°C to 85°C |
Relative humidity | 95% at 40°C, non-condensing |
Protection | NEMA-4X (IP-65) when panel mounted |
Signal Connections | |
Up/Down Totalizing | |
---|---|
Up/down totalizing is provided by a mode of the Extended counter where pulses are either added or subtracted on Channel A based on a direction input on Channel B. The counter can also be programmed so that counting by Channel A is inhibited by an input on Channel B. | |
Combining Two Totals | |
A+B, A-B and A/B arithmetic functions are available with the Extended counter. A+B sums both totals, while A-B subtracts the outflow total from inflow total. The A/B ratio applied to total helps assure the proper mixing of components. Controller setup and monitoring of the mixing operation are facilitated by optional serial communications. RS485 allows a single data line to handle multiple controllers. |
|
Up or Down Counting with Preset | |
A single Laureate dual-channel counter will handle two repetitive fill operations by counting from zero up to a preset, or down from a preset to zero. A dual setpoint relay board is required. | |
Machine Rune Time and Utilization | |
An easy way to measure the run time of machines is to count AC line cycles and scale the total to hours. To display machine utilization or duty cycle in percent, use the Extended counter. Connect Channel A to switched AC and Channel B to the AC line, and have the counter display the A/B ratio with a 100 multiplier. | |
Total and Rate Simultaneously | |
The Extended version of the Laureate dual channel counter can display scaled rate or total for the same channel at the push of a button, and alarm both the rate and total. The Extended version can also do curve linearization, thereby extending the working range and accuracy of flow transducers. | |
System-level Capabilities | |
The Laureate dual channel totalizer can independently scale, display and alarm two totals, and the totals plus alarm data can be transmitted via RS232 or RS485. The displayed totals can also be transmitted as an isolated 4-20 mA or 0-10V analog output. The Extended version can further display and transmit arithmetic combinations of the two totals. |